Shark 100B Spezifikationen Seite 39

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 114
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 38
e
Electro Industries/GaugeTech
Doc # E145701 4-5
4.5:
Voltage
and
Power
Supply
Connections
Q
Voltage Inputs are connected to the back of the unit via a optional wire connectors. The connectors
accomodate up to AWG#12 / 2.5mm wire.
Figure 4.4: Voltage Connection
4.6:
Ground
Connections
Q
The meters Ground Terminals ( ) should be connected directly to the installation’s protective earth
ground. Use 2.5mm wire for this connection.
4.7:
Voltage
Fuses
Q
EIG recommends the use of fuses on each of the sense voltages and on the control power, even
though the wiring diagrams in this chapter do not show them.
Use a 0.1 Amp fuse on each voltage input.
Use a 3 Amp fuse on the power supply.
RS-485 Output
(Do not put the
Voltage on these
terminals!)
Voltage
Inputs
Power
Supply
Inputs
Seitenansicht 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 113 114

Kommentare zu diesen Handbüchern

Keine Kommentare