e
Electro Industries/GaugeTech
Doc # E145701 D-7
Q
Phase-to-Phase Voltage ( Points 4 - 6 )
These points are formatted as 2's complement fractions. They represent a fraction of a 300 V
Secondary input. Inputs of above 300 V Secondary will be pinned at 300 V Secondary.
Q
Phase Current ( Points 7 - 9 )
These points are formatted as 2's complement fractions. They represent a fraction of a 10 A
Secondary input. Inputs of above 10A Secondary will be pinned at 10 A Secondary.
Q
Total Power ( Points 10 - 11 )
These points are formatted as 2's complement fractions. They represent a fraction of 4500 W
Secondary in normal operation, or 3000 W Secondary in Open Delta operation. Inputs above/below
+/-4500 or +/-3000 W Secondary will be pinned at +/-4500 or +/-3000 W Secondary, respectively.
Q
Total VA (Point 12 )
This point is formatted as a 2's complement fraction. It represents a fraction of 4500 W Secondary
in normal operation, or 3000 W Secondary in Open Delta operation. Inputs above/below +/-4500 or
+/-3000 W Secondary will be pinned at +/-4500 or +/-3000 W Secondary, respectively.
Point Reading
4 Phase AB Voltage
5 Phase BC Voltage
6 Phase CA Voltage
Point Reading
7 Phase A Current
8 Phase B Current
9 Phase C Current
Point Reading
10 Total Watt
11 Total VAR
Point Reading
12 Total VA