Specifications
Voltage Inputs
20-416 Volts Line To Neutral,
(Shark® 100S meter), 20-576
Volts Line to Neutral (Shark®
200S meter)
0-721 Volts Line to Line
Universal Voltage Input
Input Withstand Capability –
Meets IEEE C37.90.1 (Surge
Withstand Capability)
Programmable Voltage
Range to Any PT ratio
Supports: 3 Element WYE,
2.5 Element WYE, 2 Element
Delta, 4 Wire Delta Systems
Burden: 0.36VA per phase Max
at 600V, 0.014VA at 120 Volts
Current Inputs
Class 10: 5 Amp Nominal, 10
Amp Maximum
Class 2: 1 Amp Nominal,
2 Amp Secondary
Programmable Current to
Any CT Ratio
Burden 0.005VA per phase
Max at 11Amps
5mA Pickup Current for
Class 10
1mA Pickup Current for
Class 2
Current Surge Withstand:
100A/10 Seconds at 23° C
Isolation
All Inputs and Outputs are
galvanically isolated to 2500
Volts AC.
Environmental Rating
Storage: (-20 to +70)° C
Operating: (-20 to +70)° C
Humidity: to 95% RH
(Non-condensing)
Sensing Method
RMS
Sampling at 400+ Samples
per Cycle on all channels
measured readings
simultaneously
Harmonic %THD (% of Total
Harmonic Distortion)
- Shark® 100S meter only
Update Rate
Watts, VAR and VA - Every 6
cycles (e.g., 100ms @ 60Hz)
All other parameters - Every
60 cycles (e.g., 1s @ 60Hz)
(1 second for Current Only
measurement, if reference
voltage is not available)
Power Supply
(90 to 400) Volts AC and
(100 to 370) Volts DC.
Universal AC/DC Supply
Burden: 16VA max.
Communication Format
2 Com Ports
RS485 Port
IrDA (Through Faceplate)
Protocol Modbus RTU,
Modbus ASCII
Com Port Baud Rate: (9600
to 57600)
Com Port Address: 0-247
8 Bit, No parity
Modbus RTU or ASCII Protocols
Ethernet
802.11b Wireless
10/100BaseT Ethernet (RJ45)
Modbus TCP Protocol
Dimensions and Shipping
Weight: 4 lbs
7.9H x 7.5W x 3.1D in
20.1H x 19.1W x 7.9D cm
Meter Accuracy
See page 3
Compliance:
IEC 62053-22 (0.2%
Accuracy)
ANSI C12.20 (0.2% Accuracy)
ANSI (IEEE) C37.90.1 Surge
Withstand
ANSI C62.41 – Burst
EN61000-6-2 – Immunity for
Industrial Environments: 2005
EN61000-6-4 – Emission
Standards for Industrial
Environments: 2007
EN61326-1 EMC Requirements:
2006
UL Listed
Communication Converters
CAB 6490 – USB to IrDA Adapter for Programming
Unicom 2500 RS485 to RS232 Converter
Unicom 2500-F – RS485 to RS232 to Fiber Optic Converter
Modem Manager, Model # MM1– RS485 to RS232 Converter
for Modem Communication
Compliance Documents
Certificate of Calibration, Part #: CCal – This provides
Certificate of Calibration with NIST traceable Test Data.
Current Transformer Kits
CT200K – 200/5 Ratio 1.00” Window 3 CTs
CT400K – 400/5 Ratio, 1.25” Window, 3 CTs
CT800K – 800/5 Ratio, 2.06” Window, 3 CTs
CT2000K – 2000/5 Ratio, 3.00” Window, 3 CTs
CT Specifications:
Frequency: 50 to 400Hz; Insulation: 600 Volts, 10kV BIL
Flexible Leads: UL 1015 105°C, CSA Approved, 24” Long, #16AWG
Software Option Numbers
COMEXT3.1C – CommunicatorEXT 3.0 for Windows® (Single Lic)
COMEXT3.MC – CommunicatorEXT 3.0 for Windows® (Multi Lic)
* Consult factory application engineer for additional transformer
ratios, types or window sizes.
E-Billing EXT
Automated bill generation software for Shark®
200S Submeter only.
Additional Accessories
Electro Industries/GaugeTe ch
1800 Shames Drive • Westbury, NY 11590
1- 877-EIMETER (1- 877-346-3837) • E-Mail: [email protected]
Tel: 516-334-0870 • Web Site: www.electroind.com • Fax: 516-338-4741
E145722 031113 V1.11
Ordering Information
To order, please fill out ordering guide:
-
-
-
-
-
-
Model Frequency Current V-Switch
TM
Communication
Class Pack Format
60 10 V3 485
Shark
®
100S 50 10 V3* 485
50 Hz 5 Amp Default with RS485
System Secondary Energy Counters
(Shark® 100S)
Shark
®
200S 60 2 V4* WiFi
60 Hz 1 Amp Above with Wireless or
System Secondary Harmonics and Limits LAN Based Ethernet
(Shark® 100S)
V33**
Multi-Function Meter with
2 MB Datalogging Memory
(Shark® 200S)
-
-
®
100S/200S Submeters
SH RK
* Shark® 100S meter only
** Shark® 200S meter only
Option
Numbers:
Example: Shark
®
100S
Seitenansicht 7
1 2 3 4 5 6 7 8